- Analogue conventional detector inputs: 20 detectors or MCPs maximum.
- Smaller size and easier for installation, but all-around.
- Maximum number of bells per CIE: 4 Bells.
- 2 relay-outputs: FIRE/FAULT.
- High-capacity batteries: 12V2.3Ah*2, over 8h for stand-by use.
- Automatic power switchover: mains power and stand-by power.
- Succinct functional buttons: friendly user interface for easy operation and recognition.
- Fault supervision and notification: inputs, sounder, mains/batteries.
- Evacuation: man-made fire alarm condition on panel.
- Silence: sounders and panel buzzer.
- Extensible application for GSM: inform user anytime by mobile telephone.
AC INPUT | 220VAC 50/60Hz | +10% |
-15% | ||
DC OUTPUT | 24VDC typical | |
Voltage for MCU | 5V | |
Current @ 220VAC | standby current ≤250mA | |
Maximum current | 1A | |
Batteries current | 750mA maximum, current limited | |
Batteries | 2*12V/ 2.3Ah sealed lead acid gel, self-regulated | |
Battery low-voltage protection | 22.2V | |
The maximum and minimum electrical ratings for each input and output | Detectots / zone lines: 21V-26V Sounder1 and sounder2 lines:21-26.2V Fire protection/Fire routing/Fault routing lines:21-26.2V | |
Max points (detector and MCP) per CIE | 20 detectors and 10 MCPs | |
Zone alarm current | 6mA minimum/ 27mA maximum | |
Sounder output | 2*0.3A maximum | |
Relay contacts rating | Dry contacts (NO/NC) 1A @24VDC | |
EOL resistor for zone and outputs | 6.8K 1W | |
Fuse on EMI board | 2A/ 250V Ceramic slow blow fuse 5*20(mm) | |
Environmental | Class A temperature range: -5 to 40°C (23~104°F) Humidity: 5 to 95% RH, non-condensing | |
Terminal blocks rating | All terminals rated for 12 to18 AWG (0.75 to 2.5 mm2) | |
Service life | 10 years |