Addressable Smoke Detector features:
• Addressable-analog communication
• Low standby current for continuous
monitoring (≤2.5mA)
• Two-wire connection
• Two LEDs (RED), blinks in normal condition
and becomes stationary during fire
• Remote test from Panel
Spacing
Spacing of detector must be followed by standard EN 54 or NFPA 72. NFPA 72
suggests for low airflow application spacing of 9.1 m for ceiling height up to 3.15 m can
be applicable. However, please follow the specific codes and local codes for specific
applications.
Addressable Smoke Detector Technical parameters:
| Model No. | AW-D101 | 
| D/C | 1712 | 
| Operating Voltage Range | 18V-28VDC | 
| Alarm Current | ≤3mA | 
| Work Current | ≤2.5mA | 
| Temperature | -10℃ to 50℃ | 
| Smoke Sensitivity | 0.1-0.15 dB/m | 
| Standard Number Ref | EN 57-7:2000 | 
| Size | 99.80mm | 
| Terminals Connection | No 6: Remote Indicator+ No 3: Remote Indicator- | 
| No 2: Loop IN+ No 5: Loop IN- | 
smoke detector installation smoke detector placement
AW-D101 addressable detector use a separate base to simplify the installation and
maintenance. For proper installation, terminal connections to be followed as shown
below






 
				 
				 
				 
				 
				