Product Features
LPCB Addressable Fire Alarm System Input Output Module Feature:
1. Executive standard: EN54-18
2. Operation voltage: loop DC24V (polarity-insensitive);power DC24V(polarity-insensitive)
3. Quiescent current: loop current<0.8mA; power current<2mA
4. Action current: loop current<5mA; power current<15mA
5. Capacity of the output control contact: 1A@DC30V
6. Operation indicator: The inspection indicator will blink once about every 12 seconds in the inspection status or remain lit in
the output status; the input indicator will remain lit in the feedback status.
7. Operating environment: Temperature: -10ºC ~ 55ºC; RH: ≤95% (40 ºC±2ºC, without condensation)
8. External dimensions: 86×86×41(mm,With base)
9. Weight: about 148g(With base)
Technical parameters
LPCB Addressable Fire Alarm System Input Output Technical parameters:
| Operating Voltage | Signal Loop 24V(18V~28V) Power 24VDC(20VDC~28VDC) |
| Standby Current | Loop<0.8mA ; Power<2mA |
| Action Current | Loop<5mA ; Power<15mA |
| Output Capacity | 1A@DC30V |
| Input Mode Setting | NC or NO input mode can be set by the jumper JP4. |
| Programming Method | Electronically addressed |
| Code Range | One address within 1~324. |
| Indicators | Inspection indicator: l blink once about every 12 seconds in the inspection status or remain lit in the output status; Input indicator : remain lit in the feedback status. |
| Operating Temperature | -10℃~+55℃ |
| Relative Humidity | ≤95% , non-condensing |
| Material of Enclosure | ABS |
| Dimension (L×W×H) | 86mm×86mm×41mm (with base) |
| Mounting Hole Distance | 60.5mm |
| Weight | About 148g (with base) |